Thermal Solutions has designed the Evolution® high efficiency copper-finned water heaters to meet the needs of today's commercial domestic hot water heating requirements.

The Evolution takes the very best of existing copper-finned water heater technology to the next level by incorporating a list of design features not found in competitors' products. Real-life serviceability, innovative heat exchanger design, clean and efficient advanced combustion, and unique timesaving controls are all combined

more

Related Products

Unit of Measure

Specifications

MBH Input

750 MBtu/hour

On-Off

No

Modulating

Yes

Elect. 1-Phase

120 208 230

Elect. 3-Phase

208 230 460

Drawing


Dimensional Drawing for Evolution - High Efficiency Water Heaters

Ratings and Dimensional Data

Input: BTUH

750,000 Btu/hr

Output: BTUH

615,000 Btu/hr

Width: "A"

28.25 in717.55 mm

Depth: "C"

30.25 in768.35 mm

Height: "B"

60.938 in1547.81 mm

Gas Connection: NPT

1-1/2 in

Water Connections: NPT

3 in

Air Inlet Connection

6 in152.4 mm

Vent Connection

4 in101.6 mm

Shipping Weight

1172 Pound

Ratings & Capacities

Fuel

Natural Gas Propane

Input - High Fire

750,000 Btu/hr

Output - High Fire

615,000 Btu/hr

Boiler

180 kW

Inlet Gas Pressure (NG)

5 PSI Max. 7" W.C. Min.

Inlet Gas Pressure (LP)

2 PSI Max. 7" W.C. Min.

Operating Weight

1305 lb592 kg

Electrical Supply Options

Electrical Supply Options (Modulating)

120v/1ph/60hz - 7.5 Amps 208v/1ph/60hz - 6.6 Amps 208v/3ph/60hz - 6.0 Amps 230v/1ph/60hz - 6.4 Amps 230v/3ph/60hz - 6.0 Amps 460v/3ph/60hz - 3.0 Amps

ASME Design Data

ASME Design Data

Max. 160 PSIG & 250ºF

Trim & Controls

Trim & Controls

Blower Motor, 1-1/2 HP Combustion Air Switch Flame Safeguard High Temperature Limit High/Low Gas Press Switches LWCO Flow Switch Modulating Gas Valve Operating Control Pilot Gas Regulator Pilot Gas Valve Pilot/Leak Test Cocks Pressure & Temperature Gauge Relief Valve VFD

Double Block & Bleed (D.B.& B.) Gas Train Option

Double Block & Bleed (D.B.& B.) Gas Train Option

(1) Motorized & (1) Solenoid Gas Valves N.O. Vent Valve

D.B.& B. W/ P.O.C. Gas Train Option

IRI W/ P.O.C. Gas Train Option

(2) Motorized Gas Valves with proof of closure switches Flame Safeguard that recognizes proof of closure valves N.O. Vent Valve

Firing Modes

N/A

Evolution water heaters are available in Full Modulation. Full modulation is achieved using a VFD and an air-fuel ratio modulating control valve. The control valve is actuated by an air signal from the fan - as the fan varies so does the gas valve. It is truly a linkage-less system and allows for safe fuel-air combustion. The full modulation uses a digital operating controller for infinitely proportional firing. Full modulation is available in models 500-2000 MBH input.

The Evolution water heaters is available as a single or multi phase electric input, both 50 and 60 hertz. With no requirement for step-down transformers, the Evolution package comes complete and ready for single point electrical connection.

Evolution® Outdoor Model

N/A

A specially designed, fully UL-approved outdoor jacket enclosure allows outdoor placement and all-weather operation.

In a response to industry demand, the Evolution outdoor unit enters the scene with the same robust design as the superior indoor model. The Evolution outdoor water heaters is also designed to operate with NOx ratings below 10 ppm. Manufactured in five sizes from 500,000 to 2,000,000 BTU, the outdoor unit is available in on/off and full modulation firing modes. It is also available in both single and three-phase voltages. The outdoor model occupies the same footprint as the indoor unit, and its specially designed, fully UL-approved outdoor jacket enclosure allows outdoor placement and all-weather operation with lockable panel.

Evolution High Efficiency Domestic Hot Water Heating

N/A

Get advanced Evolution high-efficiency heating technology in a factory-assembled Packaged Water Heater System. Available in direct and indirect designs, each comes complete with storage tank, pump, and controls to serve as your single-source solution for domestic water heating needs.

Highlights

N/A

  • Ultra-low NOx levels below 10 ppm; meets or exceeds the most stringent emission requirements in the United States
  • CO less than 50 ppm
  • Quiet operation ( <50 dBA)
  • Maintenance-free ceramic radiant burner design
  • Gasketless header design; minimizes the potential for leaks
  • High quality copper-finned tubes extruded from solid copper piping; wall thickness is the best in the industry at 0.072"
  • Copper tubes are individually accessible for cleaning or inspection and replaceable to eliminate the need for whole heat exchanger replacement
  • Standard UL/FM/CSD-1 gas train; optional DB&B or IRI with POC gas train
  • Single-point electrical hook-up for all voltage options (120-208-230/1/60 and 208-230-480/3/60)
  • Multiple relief valve settings (30, 50, 60, 75, 100, 125 and 150 psig)
  • Gas pressures range from 4" wc up to 5 psig
  • Infinitely proportional firing (Modulating models only)
  • Electric spark-to-pilot-ignition system
  • Aluminum non-sparking fan assembly
  • VFD air control; no dampers or linkages (Modulating models only)
  • Inlet air filter 99% efficient to 1 micron
  • Non-proprietary parts
  • Lockable jacket design lends itself to complete access to all components for easy serviceability
  • UV resistant paint
  • Quick-connect compact package; maximum footprint is 6 sq/ft
  • Sealed combustion or room air ready
  • Reduced stack sizes - multiple venting options: sealed, direct and conventional
  • Factory fire-test on every unit 

Approvals

Approvals


cUL US, {H} Listed