Serviceable Efficiency, Exceptional Heat Transfer
Thermal Solutions' innovative gasket-less bronze header allows access to individual tubes for inspection and cleaning by mechanical or chemical methods. It also allows for individual tube replacement, unlike the "disposable" type heat exchangers already on the market. The combustion chamber is completely enclosed in a stainless steel compartment that includes collection/evaporation components to effectively handle cold-start condensate.
Clean and Efficient, Advanced Combustion
Designed to operate with NOx ratings less than 10 ppm, the Evolution's ceramic radiant burner runs at minimal excess air levels creating clean burning, highly efficient, trouble-free operation. Our rugged industrial cast aluminum blower and fan wheel are equipped with a replaceable combustion air filter 99% efficient to one micron, creating excellent combustion characteristics with ensured even air distribution.
Troubleshooting, Timesaving Diagnostic Controls
State-of-the-art microprocessor flame safeguard controls provide extensive diagnostic information - including first out fault annunciation - using a LED diagnostic display. Each water heater undergoes complete factory fire testing to fully calibrate the fuel/air mixture to pre-set precise combustion set-up and operation.
Domestic Hot Water Sizing Requirements
Commercial buildings have different domestic hot water needs. The building type will be the major variable and the following chart shows the demand based on the fixture method.
Hard Working Quality. Built to Last.
Without question, the Evolution Water Heater is the most advanced, best-designed water heater on the market. Thermal Solutions designed the Evolution Water Heater to address the realities of today’s operational environment. You can trust the Evolution Water Heater to be your reliable, efficient source of hot water for years to come.
Packaged Water Heater Systems
Thermal Solutions also offers two types of factory-assembled Packaged Water Heater Systems: Direct and Indirect Systems. Each system includes a boiler or water heater, a vertical storage tank, pump, controls and all necessary components for a totally operational, skid mounted and factory certified package.
The ASME Section IV, Part HLW tanks are certified at 125 psi MAWP. They are available with a glass or epoxy lining and with or without jacketing & insulations.
The Direct System incorporates an EVAW bronze water heater with an all bronze pump, vertical storage tank, and controls. The Indirect System uses an EVA series boiler with a cast iron pump and a heat transfer tube bundle installed in the tank. This system features a closed loop operation with the water circulating between the boiler and the heat transfer bundle.
This fully assembled, pre-packaged equipment gives the owner and designer the ease and confidence of a single-source responsibility that meets their domestic water needs.
Which System Should Be Used?
When specifying or selecting a water heating system, it is important to consider the water in your area. If water quality is questionable or if the water hardness level is 8.5 grains or more, the Indirect System should be used. The Indirect System prevents any scale from building up on the inside of the boiler tubes when properly treated water is used. This keeps the system maintenance free and prolongs the life of the water heater.
Related Products
Ratings & Capacities
Fuel |
N/A Natural Gas Propane |
Input - High Fire |
N/A 2,000,000 Btu/hr |
Output - High Fire |
N/A 1,640,000 Btu/hr |
Boiler |
N/A 481 kW |
Inlet Gas Pressure (NG) |
N/A 5 PSI Max. 9" W.C. Min. |
Inlet Gas Pressure (LP) |
N/A 2 PSI Max. 9" W.C. Min. |
Operating Weight |
N/A 1690 lb767 kg |
Water Heater Dimensions
Dimension K |
N/A 24 in |
Dimension L |
N/A 76 in |
Dimension M |
N/A 98 in |
Gas Inlet N |
N/A 1-1/2 in |
Vent Outlet P |
N/A 6 in |
Electrical Supply Options
Electrical Supply Options (Modulating) |
N/A 120v/1ph/60hz - 7.5 Amps 208v/1ph/60hz - 6.6 Amps 208v/3ph/60hz - 6.0 Amps 230v/1ph/60hz - 6.4 Amps 230v/3ph/60hz - 6.0 Amps 460v/3ph/60hz - 3.0 Amps |
Trim & Controls
Trim & Controls |
N/A Blower Motor, 1-1/2 HP Combustion Air Switch Flame Safeguard High Temperature Limit High/Low Gas Press Switches LWCO Flow Switch Modulating Gas Valve Operating Control Pilot Gas Regulator Pilot Gas Valve Pilot/Leak Test Cocks Pressure & Temperature Gauge Relief Valve VFD |
Double Block & Bleed (D.B.& B.) Gas Train Option
Double Block & Bleed (D.B.& B.) Gas Train Option |
N/A (1) Motorized & (1) Solenoid Gas Valve N.O. Vent Valve |
D.B.& B. W/ P.O.C. Gas Train Option
IRI W/ P.O.C. Gas Train Option |
N/A (2) Motorized Gas Valves with proof of closure switches Flame Safeguard that recognizes proof of closure valves N.O. Vent Valve |
Highlights
N/A
|
Packaged Systems
N/A
|